Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 19, 2019, 05:18 PM
  • 05 0480_05 0479_8192019_102152.mp4

Date
08/19/2019
W/O
0786503
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00526
PipeID
P05695
Time
10:18 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8059
Sewer Name
05 STRAWBERRY AVENUE TRUNK
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
20190819DF_STRAWBERRY_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
05 0479
Downstream MH
05 0480
Dir. of Survey
Upstream
Length Surveyed
288 ft.
Total Length
288 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 05 0479 to 05 0480
MH: 05 0479MH: 05 0480upstream0 ft. MGO - General Observation - Grease Throughout The Reach (5%)0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Ends - 10:51 AM2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish2.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish55.7 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 4"76.3 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 4"94 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Open124.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"135 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Open178.1 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 4"180.4 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Open205.9 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open216.2 ft. TFD - Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Open/25% GREASE-LATERAL221.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open254.7 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open286 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start286 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start286 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start287.9 ft. MWL - Water Level, 10 %of cross sectional area287.9 ft. MWM - Water Mark, 15 %of cross sectional area288 ft. MGO - General Observation - ROACHES @ MH288 ft. AMH - Downstream Manhole, Survey Begins - 10:20 AM

Observation photos (4)

  • Downstream Manhole, Survey Begins - 10:20 AM

    0 ft. - Downstream Manhole, Survey Begins - 10:20 AM

  • Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Open/25% GREASE-LATERAL

    71.8 ft. - Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Open/25% GREASE-LATERAL

Observations (24)

DistanceCodeObservation
232.3TFA
82.1TFOpen
163.3TFC
153TFOpen
285.9SSS
0MGOROACHES @ MH
288MGOGrease Throughout The Reach (5%)
33.3TFOpen
2DAGS
211.7TFC
0.1MWL
285.9DAGS
109.9TFA
2CM
288MGOConn. @ Mh, 9 O' Clock. Active
0AMH10:20 AM
288AMH10:51 AM
194TFOpen
66.7TFOpen
107.6TFOpen
2SSS
0.1MWM
71.8TFDOpen/25% GREASE-LATERAL
285.9CM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-08-19T10:18:43-07:00
documentation
FRANKLIN, CASTILLO, RUVALCABA
is_lateral_inspection
false