Section#4_08 0466_08 0465__8202019__I0224.mp4
2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES
2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR BROKEN & MISSING
2 ft. - General Observation - 50% MISSING TILES START
2 ft. - General Observation - MAG COAT 80% START
8.9 ft. - General Observation - 100% MISSING TILES
17.1 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORRISON BEYOUND REBAR
36.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR HANGING IN FLOW
57.1 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR HANGING IN FLOW
67 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO
118.9 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR HANGING IN FLOW
123.5 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR
179.5 ft. - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR
208.7 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - MISSING REBAR
325.4 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO
| Distance | Code | Observation |
|---|---|---|
| 0 | MWM | — |
| 17.1 | SRC | CORRISON BEYOUND REBAR |
| 67 | SRC | — |
| 118.9 | SRC | BROKEN REBAR HANGING IN FLOW |
| 343.4 | SAM | SEVERE AGG AREAS OF MISSING TILES |
| 325.4 | SRC | — |
| 208.7 | SRC | MISSING REBAR |
| 179.5 | SRC | CORRISON BEYOUND REBAR |
| 343.8 | AMH | 5:45AM |
| 0 | MWL | — |
| 2 | SAM | SEVERE AGG AREAS OF MISSING TILES |
| 2 | SRC | LONG & CIRCUM REBAR BROKEN & MISSING |
| 8.9 | MGO | 100% MISSING TILES |
| 2 | MGO | 50% MISSING TILES START |
| 0 | AMH | 5:10AM |
| 36.2 | SRC | BROKEN REBAR HANGING IN FLOW |
| 343.4 | MGO | MH CONN 3:00 ACTIVE |
| 343.4 | SRC | LONG & CIRCUM REBAR BROKEN & MISSING |
| 123.5 | SRC | LONG & CIRCUM REBAR |
| 343.4 | MGO | 80% MAG COAT FINISH |
| 0 | MGO | MH CONN 3:00 OPEN |
| 2 | MGO | MAG COAT 80% START |
| 343.4 | MGO | 100% TILES MISSING |
| 57.1 | SRC | BROKEN REBAR HANGING IN FLOW |
| 343.4 | SRC | CORRISON BEYOUND REBAR |