Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 20, 2019, 07:51 AM
  • Section#2_08 0470_08 0469__8202019__I0223.mp4

Date
08/20/2019
W/O
0782245
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00026
PipeID
P00526
Time
12:51 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0223
Sewer Name
08 216TH STREET TRUNK
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20190820MDM_216TH_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
08 0470
Downstream MH
08 0469
Dir. of Survey
Downstream
Length Surveyed
438.8 ft.
Total Length
438.8 ft.
Structural Index
5
Structural Quick
5T4P
Structural Rating
878
O&M Index
5
O&M Quick
5141
O&M Rating
9
Overall Index
5
Overall Quick
Overall Rating
887
Pipe schematic from manhole 08 0470 to 08 0469
MH: 08 0470MH: 08 0469downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:35AM0 ft. MGO - General Observation - MH CONN 9:00 ACTIVE0 ft. MGO - General Observation - MH CONN 6:00 OPEN0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES2 ft. MGO - General Observation - 100% MISSING TILES START2 ft. MGO - General Observation - 80% MAG COAT START2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG REBAR15.6 ft. MGO - General Observation - 30% MISSING TILES35 ft. MGO - General Observation - 100% MISSING TILES35 ft. MGO - General Observation - 50% MAG COAT START43.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR62.3 ft. MGO - General Observation - 50% MISSING TILES209.3 ft. MWL - Water Level, 50 %of cross sectional area209.3 ft. MWM - Water Mark, 80 %of cross sectional area263.8 ft. MGO - General Observation - 80% MAG COAT START285.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR292.8 ft. SRC - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - MISSING REBAR313.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR IN FLOW334.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR IN FLOW339.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR377.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR IN FLOW378.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORRISIN BEYOUND REBAR386.5 ft. MGO - General Observation - 100% MISING TILES 10:00 TO 2:00438.3 ft. MGO - General Observation - 80% MAG COAT FINISH438.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CORRISON BEYOUND REBAR438.3 ft. MGO - General Observation - 100% MISSING TILES FINISH438.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR BROKEN MISSING438.3 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG AREAS OF MISSING TILES438.8 ft. AMH - Downstream Manhole, Survey Ends - 3:10AM

Observation photos (17)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

  • General Observation - 100% MISSING TILES START

    2 ft. - General Observation - 100% MISSING TILES START

  • General Observation - 80% MAG COAT START

    2 ft. - General Observation - 80% MAG COAT START

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG REBAR

  • General Observation - 50% MAG COAT START

    35 ft. - General Observation - 50% MAG COAT START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    43.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • General Observation - 50% MISSING TILES

    62.3 ft. - General Observation - 50% MISSING TILES

  • Water Mark, 80 %of cross sectional area

    209.3 ft. - Water Mark, 80 %of cross sectional area

  • General Observation - 80% MAG COAT START

    263.8 ft. - General Observation - 80% MAG COAT START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    285.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - MISSING REBAR

    292.8 ft. - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - MISSING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR IN FLOW

    313.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR IN FLOW

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR IN FLOW

    334.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR IN FLOW

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR

    339.3 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR IN FLOW

    377.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR IN FLOW

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORRISIN BEYOUND REBAR

    378.3 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORRISIN BEYOUND REBAR

  • General Observation - 100% MISING TILES 10:00 TO 2:00

    386.5 ft. - General Observation - 100% MISING TILES 10:00 TO 2:00

Observations (31)

DistanceCodeObservation
339.3SRCCORRISON BEYOUND REBAR
15.6MGO30% MISSING TILES
438.3MGO80% MAG COAT FINISH
313.2SRCBROKEN REBAR IN FLOW
438.8AMH3:10AM
2SAMSEVERE AGG AREAS OF MISSING TILES
2MGO100% MISSING TILES START
0AMH2:35AM
386.5MGO100% MISING TILES 10:00 TO 2:00
0MGOMH CONN 9:00 ACTIVE
35MGO100% MISSING TILES
285.3SRCBROKEN REBAR
263.8MGO80% MAG COAT START
0MGOMH CONN 6:00 OPEN
62.3MGO50% MISSING TILES
0MWM
377.2SRCBROKEN REBAR IN FLOW
2MGO80% MAG COAT START
209.3MWL
378.3SRCCORRISIN BEYOUND REBAR
35MGO50% MAG COAT START
2SRCCIRCUM & LONG REBAR
438.3SRCCORRISON BEYOUND REBAR
292.8SRCMISSING REBAR
43.5SRCBROKEN REBAR
209.3MWM
438.3MGO100% MISSING TILES FINISH
334.6SRCBROKEN REBAR IN FLOW
0MWL
438.3SRCLONG & CIRCUM REBAR BROKEN MISSING
438.3SAMSEVERE AGG AREAS OF MISSING TILES

Properties (6)

custom_field_three
REBAR BROKEN MISSING - CORRISON BEYOUND REBAR
custom_field_two
1
customer
LACSD
datetime
2019-08-20T00:51:17-07:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection
false