Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 21, 2019, 12:04 PM
  • Section#5_02 1332_02 1331__8212019__I0226.mp4

Date
08/21/2019
W/O
0786985
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00238
PipeID
P03856
Time
5:04 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0226
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGLES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
20190821MDM_BELVEDERE_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
02 1332
Downstream MH
02 1331
Dir. of Survey
Downstream
Length Surveyed
159.9 ft.
Total Length
159.9 ft.
Structural Index
3
Structural Quick
4F31
Structural Rating
159
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
163
Pipe schematic from manhole 02 1332 to 02 1331
MH: 02 1332MH: 02 1331downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 5:10AM0 ft. MGO - General Observation - MH CONN 9:00 OPEN0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG11.9 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6" - STUB15.1 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG23.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB39 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN42.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE43.6 ft. MWM - Water Mark, 20 %of cross sectional area43.6 ft. MWL - Water Level, 10 %of cross sectional area43.6 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG43.6 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG59.6 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG68.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN109.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETYE SEVRE AGG ATTACHED110.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE VAGG ATTACHED122 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED159.2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG159.2 ft. MGO - General Observation - MH CONN 3:00 ACTIVE159.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE SEVERE AGG ATTACHED159.2 ft. MGO - General Observation - MH CONN 9:00 OPEN159.9 ft. AMH - Downstream Manhole, Survey Ends - 5:30AM

Observation photos (7)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

    15.1 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    43.6 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    59.6 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETYE SEVRE AGG ATTACHED

    109.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETYE SEVRE AGG ATTACHED

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE VAGG ATTACHED

    110.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE VAGG ATTACHED

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    122 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

Observations (24)

DistanceCodeObservation
159.2SAMSEVERE AGG
15.1SAMSEVERE AGG
42.1FLHAIRLINE
23.8TFCSTUB
68.9TFOPEN
43.6MWM
159.9AMH5:30AM
109.8SSSPEELING CONCRETYE SEVRE AGG ATTACHED
110.8SSSPEELING CONCRETE SEVERE VAGG ATTACHED
59.6SAMSEVERE AGG
159.2MGOMH CONN 3:00 ACTIVE
0MWM
43.6MWL
39TFOPEN
159.2SSSPEELING CONCRETE SEVERE AGG ATTACHED
0AMH5:10AM
43.6SAMSEVERE AGG
11.9TFCSTUB
122SSSPEELING CONCRETE SEVERE AGG ATTACHED
2SAMSEVERE AGG
0MGOMH CONN 9:00 OPEN
43.6SAMSEVERE AGG
0MWL
159.2MGOMH CONN 9:00 OPEN

Properties (6)

custom_field_three
PEELING CONCRETE SEVERE AGG ATTACHED
custom_field_two
2
customer
LACSD
datetime
2019-08-21T05:04:11-07:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection
false