Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 16, 2015, 06:38 AM
  • 02 0221_02 0220_16092015_000722.mp4

Date
09/15/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02527
Time
11:38 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2746
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0221
Downstream MH
02 0220
Dir. of Survey
Downstream
Length Surveyed
358.2 ft.
Total Length
358.2 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 0221 to 02 0220
MH: 02 0221MH: 02 0220downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - SERVICE LATERAL AT 3 O' CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Begins - 02 02210 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH0 ft. MWL - Water Level, 15 %of cross sectional area4.1 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES10.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start34.8 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO87.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"91.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"196.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"200.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"284.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"287.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"299.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"358.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0220A358.2 ft. MGO - General Observation - MH#S WRONG ON DATABASE358.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish358.2 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH

Observations (19)

DistanceCodeObservation
287.4TFC
0MWM
91.3TFA
358.2AMH02 0220A
4.1CM
358.2MGOMH#S WRONG ON DATABASE
358.2CM
34.8DSZ
0MGOSERVICE LATERAL AT 3 O' CLOCK AT MH
200.4TFC
10.9CM
87.8TF
0AMH02 0221
299.7TF
284.3TFC
0MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
0MWL
358.2MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
196.7TFC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-15T23:38:50-07:00
documentation
PROPIPE
is_lateral_inspection
false