Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 8, 2015, 12:33 PM
  • 02 0279_02 0278_08092015_054705.mp4

Date
09/08/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02593
Time
5:33 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2738
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
22
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0279
Downstream MH
02 0278
Dir. of Survey
Downstream
Length Surveyed
270.3 ft.
Total Length
270.3 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
16
Pipe schematic from manhole 02 0279 to 02 0278
MH: 02 0279MH: 02 0278downstream0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 02790 ft. MWL - Water Level, 10 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start20.6 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES81.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES89.1 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES93.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES98.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"199 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"270.3 ft. MGO - General Observation - LATERAL AT MH 3 0CLOCK270.3 ft. AMH - Downstream Manhole, Survey Ends - 02 0278270.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish270.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish

Observations (14)

DistanceCodeObservation
93.5CM
98.9TFC
0MWM
2.1DAGS
20.6CL
270.3MGOLATERAL AT MH 3 0CLOCK
89.1CL
0AMH02 0279
270.3AMH02 0278
0MWL
270.3CM
199TFC
81.8CM
270.3DAGS

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-08T05:33:22-07:00
documentation
PROPIPE
is_lateral_inspection
false