Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 8, 2015, 12:52 PM
  • 02 0278_02 0277_08092015_061132.mp4

Date
09/08/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02592
Time
5:52 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2738
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
22
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0278
Downstream MH
02 0277
Dir. of Survey
Downstream
Length Surveyed
379.7 ft.
Total Length
379.7 ft.
Structural Index
3
Structural Quick
3423
Structural Rating
18
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
20
Pipe schematic from manhole 02 0278 to 02 0277
MH: 02 0278MH: 02 0277downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 3 0CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 02786.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start26.5 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES42.2 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES43.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"49.1 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES90.5 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES97.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES109.6 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES121.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start127.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"247.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"327.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"375.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish379.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish379.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0277

Observations (19)

DistanceCodeObservation
26.5CL
6.7DAGS
0MWL
127.6TFC
109.6CL
42.2CM
97.1CM
379.7DAGS
121.4CM
327.5TFC
43.6TFC
49.1CM
247.4TF
0MWM
0MGOLATERAL AT MH 3 0CLOCK
379.7AMH02 0277
375.7CM
0AMH02 0278
90.5CL

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-08T05:52:48-07:00
documentation
PROPIPE
is_lateral_inspection
false