Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 10, 2015, 07:02 AM
  • 02 0261_02 0260_10092015_003235.mp4

Date
09/10/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02572
Time
12:02 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2740
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0261
Downstream MH
02 0260
Dir. of Survey
Downstream
Length Surveyed
362.4 ft.
Total Length
362.4 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 0261 to 02 0260
MH: 02 0261MH: 02 0260downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - CAPPED LATERAL AT 9 O' CLOCK AT0 ft. AMH - Upstream Manhole, Survey Begins - 02 02610 ft. MGO - General Observation - SERVICE LATERAL AT 3 O' CLOCK AT MH4.9 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES4.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start8.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start74.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"138.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"182 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"230.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"290.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"357.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish362.4 ft. MGO - General Observation - CAPPED LATERAL AT 9 O' CLOCK AT362.4 ft. AMH - Downstream Manhole, Survey Ends - 02 0260362.4 ft. MGO - General Observation - CAPPED LATERAL AT 3 O' CLOCK AT MH362.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish

Observations (18)

DistanceCodeObservation
8.2CM
0MWL
0MWM
230.2TFC
0MGOCAPPED LATERAL AT 9 O' CLOCK AT
182TFC
362.4MGOCAPPED LATERAL AT 9 O' CLOCK AT
0AMH02 0261
362.4AMH02 0260
362.4MGOCAPPED LATERAL AT 3 O' CLOCK AT MH
290.7TF
4.9CM
362.4DAGS
4.9DAGS
74.5TFC
138.7TF
357.1CM
0MGOSERVICE LATERAL AT 3 O' CLOCK AT MH

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-10T00:02:26-07:00
documentation
PROPIPE
is_lateral_inspection
false