Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 8, 2015, 08:50 AM
  • 02 0287_02 0286_08092015_020504.mp4

Date
09/08/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02601
Time
1:50 AM
Certificate
U-5087069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2738
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
22
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0287
Downstream MH
02 0286
Dir. of Survey
Downstream
Length Surveyed
291.2 ft.
Total Length
291.2 ft.
Structural Index
3
Structural Quick
3521
Structural Rating
17
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
19
Pipe schematic from manhole 02 0287 to 02 0286
MH: 02 0287MH: 02 0286downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 02870 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start5.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES10.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"30 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"52.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES68.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES77.3 ft. CM - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES85 ft. CM - Crack Multiple, from 03 to 04 o'clock, within 8 inches of joint: YES106.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"112.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start214.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"288.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish288.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish291.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0286

Observations (17)

DistanceCodeObservation
5.3CM
0AMH02 0287
214.9TFA
85CM
2.2DAGS
10.3TFC
291.2AMH02 0286
30TBA
288.5DAGS
0MWM
52.9CL
68.5CM
77.3CM
106.4TFA
112.5CM
288.5CM
0MWL

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-08T01:50:10-07:00
documentation
PROPIPE
is_lateral_inspection