Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 10, 2015, 08:42 AM
  • 02 0263_02 0262A_10092015_015546.mp4

Date
09/10/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02575
Time
1:42 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2740
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0262A
Downstream MH
02 0263
Dir. of Survey
Upstream
Length Surveyed
325.5 ft.
Total Length
325.5 ft.
Structural Index
2
Structural Quick
3111
Structural Rating
4
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 02 0262A to 02 0263
MH: 02 0262AMH: 02 0263upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 02630 ft. MGO - General Observation - CAPPED LATERAL AT 12 O' CLOCK AT MH0 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH5.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish5.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish77.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"129.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"245.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"289.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"308.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start316.3 ft. CC - Crack Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES323.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start325.5 ft. MGO - General Observation - CAPPED LATERAL AT 3 O' CLOCK AT MH325.5 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH325.5 ft. MWM - Water Mark, 40 %of cross sectional area325.5 ft. AMH - Downstream Manhole, Survey Begins - 02 0262A325.5 ft. MWL - Water Level, 5 %of cross sectional area

Observations (17)

DistanceCodeObservation
196.2TFC
9.2CC
247.6TF
36.2TFC
325.5AMH02 0263
0MGOCAPPED LATERAL AT 3 O' CLOCK AT MH
319.7CM
2.4DAGS
0MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
0MWM
0AMH02 0262A
0MWL
17.4CM
319.7DAGS
80TF
325.5MGOCAPPED LATERAL AT 12 O' CLOCK AT MH
325.5MGOSERVICE LATERAL AT 9 O'CLOCK AT MH

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-10T01:42:46-07:00
documentation
PROPIPE
is_lateral_inspection
false