Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 10, 2015, 09:33 AM
  • 02 0256_02 0255_10092015_025307.mp4

Date
09/10/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02565
Time
2:33 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2740
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0256
Downstream MH
02 0255
Dir. of Survey
Downstream
Length Surveyed
392.1 ft.
Total Length
392.1 ft.
Structural Index
3
Structural Quick
3511
Structural Rating
16
O&M Index
2
O&M Quick
4133
O&M Rating
16
Overall Index
2
Overall Quick
Overall Rating
32
Pipe schematic from manhole 02 0256 to 02 0255
MH: 02 0256MH: 02 0255downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 02560 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area5 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES26.1 ft. RFJ - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YESR27.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"28.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES135.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"135.6 ft. RBL - Roots Ball Lateral, at 12 o'clock, 85 %, within 8 inches of joint: NO135.6 ft. RMC - Roots Medium Connection, at 12 o'clock, 20 %, within 8 inches of joint: NO232.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"273.5 ft. RFJ - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YESR273.5 ft. RFJ - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YESR275.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"297 ft. CM - Crack Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES335.9 ft. RML - Roots Medium Lateral, at 12 o'clock, 30 %, within 8 inches of joint: NO335.9 ft. RMC - Roots Medium Connection, at 12 o'clock, 15 %, within 8 inches of joint: NO335.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"341.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES368.5 ft. CC - Crack Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES384.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES392.1 ft. AMH - Downstream Manhole, Survey Ends - 02 0255

Observations (22)

DistanceCodeObservation
232.2TFC
5CM
27.6TF
368.5CC
273.5RFJ
26.1RFJ
392.1AMH02 0255
135.6TFA
384.6CM
275.8TF
335.9RML
0AMH02 0256
135.6RBL
297CM
135.6RMC
335.9RMC
341.2CM
0MWL
273.5RFJ
335.9TF
28.6CM
0MWM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-10T02:33:48-07:00
documentation
PROPIPE
is_lateral_inspection
false