Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2015, 06:10 AM
  • 02 0204_02 0203A_17092015_235301.mp4

Date
09/17/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02513
Time
11:10 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2748
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 0204
Downstream MH
02 0203A
Dir. of Survey
Downstream
Length Surveyed
328.7 ft.
Total Length
328.7 ft.
Structural Index
3
Structural Quick
3322
Structural Rating
13
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 02 0204 to 02 0203A
MH: 02 0204MH: 02 0203Adownstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - SERVICE LATERAL AT 3 O' CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Begins - 02 02040 ft. MWL - Water Level, 20 %of cross sectional area14.8 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start47.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"57 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES91.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"142 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"143.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"144.7 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES183 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES189 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"194.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"241.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"246.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"253.5 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES291.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"293.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"313.2 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES326.2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish328.6 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH328.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0203A

Observations (23)

DistanceCodeObservation
91.2TF
0MWM
328.6MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
143.8TFC
183CM
194.2TFC
313.2CL
326.2DSZ
0MGOSERVICE LATERAL AT 3 O' CLOCK AT MH
328.7AMH02 0203A
293.1TFC
189TFC
14.8DSZ
246.3TF
142TFC
253.5CM
0AMH02 0204
144.7CL
291.5TFC
57CM
0MWL
241.1TF
47.7TFC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-17T23:10:41-07:00
documentation
PROPIPE
is_lateral_inspection
false