Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2015, 08:34 AM
  • 02 0205_02 0204_18092015_014840.mp4

Date
09/18/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02514
Time
1:34 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2748
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 0205
Downstream MH
02 0204
Dir. of Survey
Downstream
Length Surveyed
347.8 ft.
Total Length
347.8 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 02 0205 to 02 0204
MH: 02 0205MH: 02 0204downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 020539.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"88.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"91.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"137.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"189.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"192 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"199.5 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES202.5 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES219.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"238 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"286.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"289.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"320.2 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 8"335.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"338.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"347.8 ft. MGO - General Observation - SERVICE LATERAL AT 3 O' CLOCK AT MH347.8 ft. AMH - Downstream Manhole, Survey Ends - 02 0204

Observations (21)

DistanceCodeObservation
0MWM
347.8MGOSERVICE LATERAL AT 3 O' CLOCK AT MH
0MWL
39.4TFC
0AMH02 0205
338.7TFC
189.1TFC
238TFC
91.4TF
137.2TFC
199.5CM
320.2TF
289.7TFC
286.9TFC
192TFC
347.8AMH02 0204
335.7TFA
219.6TF
140.2TFC
202.5CM
88.5TFC