Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 8, 2015, 08:05 AM
  • 02 0288_02 0287_08092015_014946.mp4

Date
09/08/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02602
Time
1:05 AM
Certificate
U-5087069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2738
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
22
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0288
Downstream MH
02 0287
Dir. of Survey
Downstream
Length Surveyed
291.4 ft.
Total Length
291.4 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 0288 to 02 0287
MH: 02 0288MH: 02 0287downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 02880 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area3.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES7.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start97.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"195.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"286 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish288.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish291.4 ft. AMH - Downstream Manhole, Survey Ends - 02 0287

Observations (11)

DistanceCodeObservation
11DAGS
7.3CM
0AMH02 0288
291.4AMH02 0287
286CM
3.7CM
97.5TFC
288.9DAGS
0MWL
0MWM
195.3TFC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-08T01:05:03-07:00
documentation
PROPIPE
is_lateral_inspection
false