Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 15, 2015, 09:53 AM
  • 02 0233_02 0232A_15092015_030644.mp4

Date
09/15/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02541
Time
2:53 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2745
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0232A
Downstream MH
02 0233
Dir. of Survey
Upstream
Length Surveyed
350.3 ft.
Total Length
350.3 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 02 0232A to 02 0233
MH: 02 0232AMH: 02 0233upstream0 ft. MGO - General Observation - SERVICE LATERAL AT 3 O' CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Ends - 02 02333 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish8.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish17.9 ft. SSS - Surface Spalling, at 12 o'clock, within 8 inches of joint: NO73.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"76.2 ft. RML - Roots Medium Lateral, at 10 o'clock, 20 %, within 8 inches of joint: NO76.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"167.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"171.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"271.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"274.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"310.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start339 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start339 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES350.3 ft. MWL - Water Level, 15 %of cross sectional area350.3 ft. AMH - Downstream Manhole, Survey Begins - 02 0232A350.3 ft. MWM - Water Mark, 35 %of cross sectional area

Observations (18)

DistanceCodeObservation
350.3MGOSERVICE LATERAL AT 3 O' CLOCK AT MH
179TF
0MWL
78.5TFC
274TF
76.2TF
350.3AMH02 0233
182.4TFC
11.3DAGS
0AMH02 0232A
347.3DAGS
11.3CM
332.4SSS
40CM
274.1RML
0MWM
342CM
277.2TFC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-15T02:53:51-07:00
documentation
PROPIPE
is_lateral_inspection
false