Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 16, 2015, 09:42 AM
  • 02 0215A_02 0215_16092015_025946.mp4

Date
09/16/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02521
Time
2:42 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2746
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0215A
Downstream MH
02 0215
Dir. of Survey
Downstream
Length Surveyed
375.8 ft.
Total Length
375.8 ft.
Structural Index
3
Structural Quick
3400
Structural Rating
12
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole 02 0215A to 02 0215
MH: 02 0215AMH: 02 0215downstream0 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 0215A0 ft. MGO - General Observation - SERVICE LATERAL AT 3 O' CLOCK AT MH0 ft. MWM - Water Mark, 20 %of cross sectional area14.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES25.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES36 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES41 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start81 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"85.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"138 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"159.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"188 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"198 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"219.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"240.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"262.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"284.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"338.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"350.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"375.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish375.8 ft. AMH - Downstream Manhole, Survey Ends - 02 0215

Observations (23)

DistanceCodeObservation
188TF
41CM
14.8CM
36CM
375.8CM
262.2TF
219.4TF
338.5TF
0MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
81TF
138TF
85.1TF
375.8AMH02 0215
240.6TF
198TF
25.5CM
0MWL
0AMH02 0215A
0MGOSERVICE LATERAL AT 3 O' CLOCK AT MH
350.6TF
159.6TF
284.4TF
0MWM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-16T02:42:14-07:00
documentation
PROPIPE
is_lateral_inspection
false