Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 21, 2015, 10:13 AM
  • 02 0197_02 0196_21092015_032401.mp4

Date
09/21/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02505
Time
3:13 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2749
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 0197
Downstream MH
02 0196
Dir. of Survey
Downstream
Length Surveyed
324 ft.
Total Length
324 ft.
Structural Index
2
Structural Quick
3111
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 02 0197 to 02 0196
MH: 02 0197MH: 02 0196downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 01970 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH0 ft. MWL - Water Level, 15 %of cross sectional area30.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"82.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"85.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"132.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"135.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"158.8 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES182 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"185.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"231.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"234.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"284.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"287 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"319 ft. CC - Crack Circumferential, from 11 to 04 o'clock, within 8 inches of joint: YES324 ft. AMH - Downstream Manhole, Survey Ends - 02 0196324 ft. MGO - General Observation - SERVICE LATERAL AT 3 O' CLOCK AT MH

Observations (19)

DistanceCodeObservation
132.4TFC
234.9TFC
231.4TFC
182TFC
319CC
0AMH02 0197
0MWM
0MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
324AMH02 0196
284.2TFC
158.8CM
185.4TF
85.8TFC
0MWL
324MGOSERVICE LATERAL AT 3 O' CLOCK AT MH
82.7TFC
135.1TFC
287TFC
30.5TFC

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2015-09-21T03:13:04-07:00
documentation
PROPIPE
is_lateral_inspection
false