Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2015, 08:11 AM
  • 02 0207_02 0206_18092015_012211.mp4

Date
09/18/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02516
Time
1:11 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2748
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0207
Downstream MH
02 0206
Dir. of Survey
Downstream
Length Surveyed
280.2 ft.
Total Length
280.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 02 0207 to 02 0206
MH: 02 0207MH: 02 0206downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 02070 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - SERVICE LATERAL AT 3 O' CLOCK AT MH0 ft. MGO - General Observation - CAPPED LATERAL AT 9 O' CLOCK AT3.3 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES34.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"40.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"81.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"111.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"139.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"143.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"183.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"229.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"235.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"280.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0206

Observations (16)

DistanceCodeObservation
3.3CM
40.7TF
143.1TFA
0MWM
0AMH02 0207
280.2AMH02 0206
34.5TFC
139.8TFC
0MWL
81.1TFC
0MGOSERVICE LATERAL AT 3 O' CLOCK AT MH
111.5TFA
0MGOCAPPED LATERAL AT 9 O' CLOCK AT
235.9TFC
229.8TFC
183.6TFC

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2015-09-18T01:11:26-07:00
documentation
PROPIPE
is_lateral_inspection
false