Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 15, 2015, 09:35 AM
  • 02 0232_02 0231_15092015_024826.mp4

Date
09/15/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02539
Time
2:35 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2745
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0231
Downstream MH
02 0232
Dir. of Survey
Upstream
Length Surveyed
287.5 ft.
Total Length
287.5 ft.
Structural Index
3
Structural Quick
3321
Structural Rating
11
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 02 0231 to 02 0232
MH: 02 0231MH: 02 0232upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 02320 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH5.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish5.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish72.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"75.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"164.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"167 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"233.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start246.3 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES250.6 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES258.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"262.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"273.7 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES280.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start287.5 ft. MWL - Water Level, 10 %of cross sectional area287.5 ft. AMH - Downstream Manhole, Survey Begins - 02 0231287.5 ft. MWM - Water Mark, 35 %of cross sectional area287.5 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH

Observations (19)

DistanceCodeObservation
24.8TF
53.6CM
215TFC
281.8CM
0MWL
120.5TF
0AMH02 0231
6.9DAGS
13.8CM
36.9CM
287.5AMH02 0232
0MWM
0MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
41.2CL
123.3TFC
29TFC
287.5MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
281.8DAGS
211.6TF

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-15T02:35:48-07:00
documentation
PROPIPE
is_lateral_inspection
false