Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 10, 2015, 07:03 AM
  • 02 0260_02 0259_10092015_004646.mp4

Date
09/10/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02571
Time
12:03 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2740
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0260
Downstream MH
02 0259
Dir. of Survey
Downstream
Length Surveyed
392.2 ft.
Total Length
392.2 ft.
Structural Index
3
Structural Quick
3500
Structural Rating
15
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
17
Pipe schematic from manhole 02 0260 to 02 0259
MH: 02 0260MH: 02 0259downstream0 ft. MGO - General Observation - CAPPED LATERAL AT 9 O' CLOCK AT0 ft. AMH - Upstream Manhole, Survey Begins - 02 02600 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CAPPED LATERAL AT 3 O' CLOCK AT MH2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start3.1 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES6.7 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES11.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start101 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish113.2 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES118.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start216.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"327.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"388.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish392.2 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH392.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0259392.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish

Observations (18)

DistanceCodeObservation
392.2MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
2.4DAGS
113.2CM
388.8CM
0MGOCAPPED LATERAL AT 9 O' CLOCK AT
11.1CM
392.2AMH02 0259
0AMH02 0260
118.1CM
0MWM
0MWL
327.7TFC
216.6TFC
3.1CM
392.2DAGS
6.7CM
101CM
0MGOCAPPED LATERAL AT 3 O' CLOCK AT MH

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-10T00:03:13-07:00
documentation
PROPIPE
is_lateral_inspection
false