Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 15, 2015, 08:18 AM
  • 02 0244_02 0243_15092015_013357.mp4

Date
09/15/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02552
Time
1:18 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2745
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0244
Downstream MH
02 0243
Dir. of Survey
Downstream
Length Surveyed
386.4 ft.
Total Length
386.4 ft.
Structural Index
3
Structural Quick
3622
Structural Rating
22
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
24
Pipe schematic from manhole 02 0244 to 02 0243
MH: 02 0244MH: 02 0243downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 02443.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES18.6 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES31.9 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES41.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"73.7 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES107.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES111.5 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES133.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"134.6 ft. CM - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES138.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start233.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"322.5 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start329.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"381 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish381 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish386.4 ft. AMH - Downstream Manhole, Survey Ends - 02 0243

Observations (19)

DistanceCodeObservation
3.1CM
138.4CM
111.5CL
381CM
322.5DSZ
386.4AMH02 0243
0MWM
73.7CM
0MWL
134.6CM
31.9CM
381DSZ
329.8TFC
133.4TFC
0AMH02 0244
107.7CM
41.2TFC
18.6CL
233.7TFC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-15T01:18:10-07:00
documentation
PROPIPE
is_lateral_inspection
false