Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 17, 2015, 05:21 AM
  • 02 0213_02 0212_16092015_223952.mp4

Date
09/16/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02518
Time
10:21 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2747
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0213
Downstream MH
02 0212
Dir. of Survey
Downstream
Length Surveyed
345.1 ft.
Total Length
345.1 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 02 0213 to 02 0212
MH: 02 0213MH: 02 0212downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 02130 ft. MWL - Water Level, 15 %of cross sectional area4.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"53.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"68.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"72.7 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES84.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"100.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"119 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"121.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"143.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"144.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES157 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start158.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"173.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"176.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"223.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"229.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"276.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"282.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"340.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish345.1 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH345.1 ft. MGO - General Observation - SERVICE LATERAL AT 3 O' CLOCK AT MH345.1 ft. AMH - Downstream Manhole, Survey Ends - 02 0212

Observations (25)

DistanceCodeObservation
84.2TF
0MWM
144.9CM
119TF
0AMH02 0213
176.9TF
53.4TFC
345.1MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
121.5TF
72.7CM
276.2TF
157CM
68.8TF
173.9TFC
345.1MGOSERVICE LATERAL AT 3 O' CLOCK AT MH
158.2TFC
340.5CM
282.3TFC
0MWL
223.6TF
143.1TFC
100.1TFC
345.1AMH02 0212
229.7TF
4.9TF

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-16T22:21:52-07:00
documentation
PROPIPE
is_lateral_inspection
false