Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 15, 2015, 09:48 AM
  • 02 0232A_02 0232_15092015_025314.mp4

Date
09/15/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02540
Time
2:48 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2745
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0232
Downstream MH
02 0232A
Dir. of Survey
Upstream
Length Surveyed
52.4 ft.
Total Length
52.4 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 0232 to 02 0232A
MH: 02 0232MH: 02 0232Aupstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 0232A2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish4.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish34.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"36.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"43.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start48.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES49.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start52.4 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH52.4 ft. MWM - Water Mark, 35 %of cross sectional area52.4 ft. MWL - Water Level, 15 %of cross sectional area52.4 ft. AMH - Downstream Manhole, Survey Begins - 02 0232

Observations (12)

DistanceCodeObservation
0MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
49.9DAGS
9CM
2.5DAGS
47.6CM
18.1TFC
15.7TF
0MWM
0MWL
0AMH02 0232
52.4AMH02 0232A
4.1CM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-15T02:48:46-07:00
documentation
PROPIPE
is_lateral_inspection
false