Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 11, 2015, 08:04 AM
  • 02 0252_02 0251_11092015_011857.mp4

Date
09/11/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02561
Time
1:04 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2743
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0252
Downstream MH
02 0251
Dir. of Survey
Downstream
Length Surveyed
363.1 ft.
Total Length
363.1 ft.
Structural Index
2
Structural Quick
3423
Structural Rating
19
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
19
Pipe schematic from manhole 02 0252 to 02 0251
MH: 02 0252MH: 02 0251downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 02520 ft. MWM - Water Mark, 5 %of cross sectional area20.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES33.5 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES94.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"189.2 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES198.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"212.7 ft. CC - Crack Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES252.4 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES288.1 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES294.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"340.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES349.5 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES363.1 ft. AMH - Downstream Manhole, Survey Ends - 02 0251363.1 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH

Observations (16)

DistanceCodeObservation
94.8TFC
252.4CL
189.2CM
363.1AMH02 0251
198.8TFA
0MWL
0AMH02 0252
349.5CL
212.7CC
363.1MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
294.5TFC
288.1CM
0MWM
340.6CM
20.6CM
33.5CL

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-11T01:04:49-07:00
documentation
PROPIPE
is_lateral_inspection
false