Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 10, 2015, 08:23 AM
  • 02 0262_02 0261_10092015_013626.mp4

Date
09/10/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02573
Time
1:23 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2740
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0261
Downstream MH
02 0262
Dir. of Survey
Upstream
Length Surveyed
327 ft.
Total Length
327 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 0261 to 02 0262
MH: 02 0261MH: 02 0262upstream0 ft. MGO - General Observation - CAPPED LATERAL AT 3 O' CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Ends - 02 02620 ft. MGO - General Observation - CAPPED LATERAL AT 9 O' CLOCK AT1.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish5.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish55.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"106.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"142.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"222.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"266.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"309.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start311.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES324.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start327 ft. MWL - Water Level, 10 %of cross sectional area327 ft. MGO - General Observation - CAPPED LATERAL AT 3 O' CLOCK AT MH327 ft. AMH - Downstream Manhole, Survey Begins - 02 0261327 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH327 ft. MWM - Water Mark, 40 %of cross sectional area

Observations (18)

DistanceCodeObservation
104.3TFA
0MWL
327MGOCAPPED LATERAL AT 3 O' CLOCK AT MH
60.9TFC
184.7TFA
0MGOCAPPED LATERAL AT 3 O' CLOCK AT MH
17.9CM
0AMH02 0261
325.4DAGS
220.4TFC
0MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
15.8CM
321.9CM
2.1DAGS
271.8TF
327AMH02 0262
327MGOCAPPED LATERAL AT 9 O' CLOCK AT
0MWM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-10T01:23:36-07:00
documentation
PROPIPE
is_lateral_inspection
false