Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 15, 2015, 10:58 AM
  • 02 0230_02 0229A_15092015_040245.mp4

Date
09/15/2015
W/O
521010
Weather
Light Rain
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02537
Time
3:58 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2745
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0230
Downstream MH
02 0229A
Dir. of Survey
Downstream
Length Surveyed
81.2 ft.
Total Length
81.2 ft.
Structural Index
3
Structural Quick
3321
Structural Rating
11
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole 02 0230 to 02 0229A
MH: 02 0230MH: 02 0229Adownstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 023013.4 ft. CM - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES17.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES22.4 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES28.8 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start60.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"63.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"77.4 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish81.2 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH81.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0229A

Observations (12)

DistanceCodeObservation
81.2MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
0MWM
17.6CM
81.2AMH02 0229A
63.6TF
22.4CL
60.9TFC
28.8CM
77.4CM
0MWL
0AMH02 0230
13.4CM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-15T03:58:16-07:00
documentation
PROPIPE
is_lateral_inspection
false