Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 8, 2015, 11:22 AM
  • 02 0280_02 0279_08092015_043121.mp4

Date
09/08/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02594
Time
4:22 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2738
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
22
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0279
Downstream MH
02 0280
Dir. of Survey
Upstream
Length Surveyed
62.3 ft.
Total Length
62.3 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole 02 0279 to 02 0280
MH: 02 0279MH: 02 0280upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 02800 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES22.9 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES60 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start60.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"62.3 ft. MWM - Water Mark, 50 %of cross sectional area62.3 ft. MWL - Water Level, 10 %of cross sectional area62.3 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK62.3 ft. AMH - Downstream Manhole, Survey Begins - 02 0279

Observations (10)

DistanceCodeObservation
0MWM
0MWL
0MGOLATERAL AT MH 9 OCLOCK
2.3DAGS
55.3CM
62.3AMH02 0280
0AMH02 0279
39.4CM
2.1TFC
62.3DAGS

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-08T04:22:37-07:00
documentation
PROPIPE
is_lateral_inspection
false