Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 10, 2015, 05:36 AM
  • 02 0265_02 0264_09092015_232852.mp4

Date
09/09/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02579
Time
10:36 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2740
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0265
Downstream MH
02 0264
Dir. of Survey
Downstream
Length Surveyed
333.1 ft.
Total Length
333.1 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 02 0265 to 02 0264
MH: 02 0265MH: 02 0264downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CAPPED LATERAL AT 3 O' CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Begins - 02 02650 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CAPPED LATERAL AT 9 O' CLOCK AT3.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start5.5 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES21 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES33.5 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES36.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start68.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"110.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"167 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"214.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"261.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"300.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"325.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish330 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish333.1 ft. AMH - Downstream Manhole, Survey Ends - 02 0264

Observations (19)

DistanceCodeObservation
333.1AMH02 0264
0MWL
0MGOCAPPED LATERAL AT 3 O' CLOCK AT MH
5.5CL
0AMH02 0265
3.1DAGS
33.5CL
214.3TFC
36.9CM
261.3TF
110.5TFA
330DAGS
325.4CM
167TF
0MWM
68.1TFC
21CM
0MGOCAPPED LATERAL AT 9 O' CLOCK AT
300.5TFA

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-09T22:36:39-07:00
documentation
PROPIPE
is_lateral_inspection
false