Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 23, 2015, 07:57 AM
  • 02 0196_02 0195_21092015_020101.mp4

Date
09/23/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02504
Time
12:57 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2750
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 0196
Downstream MH
02 0195
Dir. of Survey
Downstream
Length Surveyed
387.9 ft.
Total Length
387.9 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 02 0196 to 02 0195
MH: 02 0196MH: 02 0195downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 01960 ft. MGO - General Observation - SERVICE LATERAL AT 3 O' CLOCK AT MH0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area54.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"57.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"104 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"107.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"156.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"159.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"206.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"209.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"256 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"258.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"263.3 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES288.1 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES304.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"307.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"354.2 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"357.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"387.9 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH387.9 ft. AMH - Downstream Manhole, Survey Ends - 02 0195

Observations (22)

DistanceCodeObservation
159.9TFC
104TFC
263.3CL
107.1TF
387.9MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
206.4TFC
0AMH02 0196
288.1CL
54.5TFC
304.9TFC
0MGOSERVICE LATERAL AT 3 O' CLOCK AT MH
156.8TFC
307.6TFC
57.4TF
357.6TFC
0MWL
256TFC
209.2TF
0MWM
354.2TBC
387.9AMH02 0195
258.5TFC

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2015-09-23T00:57:17-07:00
documentation
PROPIPE
is_lateral_inspection
false