Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 24, 2015, 08:19 AM
  • 02 0177_02 0176A_24092015_013104.mp4

Date
09/24/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02484
Time
1:19 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2751
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
32
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 0177
Downstream MH
02 0176A
Dir. of Survey
Downstream
Length Surveyed
289.2 ft.
Total Length
289.2 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 02 0177 to 02 0176A
MH: 02 0177MH: 02 0176Adownstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 01770 ft. MWM - Water Mark, 30 %of cross sectional area13.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES18.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"21.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"66.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"69.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"114.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"117.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"149.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES153.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"157.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"217.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"220.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"269.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"272.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"289.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0176A289.2 ft. MGO - General Observation - SERVICE LATERAL AT 3 O' CLOCK AT MH

Observations (19)

DistanceCodeObservation
220.7TFC
157.2TF
289.2AMH02 0176A
269.9TFC
18.2TFC
114.6TFC
66.7TFC
289.2MGOSERVICE LATERAL AT 3 O' CLOCK AT MH
0MWL
153.7TFC
217.8TFC
117.8TFC
21.2TFC
13.6CL
149.2CL
0AMH02 0177
69.8TFC
272.8TFC
0MWM

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2015-09-24T01:19:48-07:00
documentation
PROPIPE
is_lateral_inspection
false