Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 8, 2015, 01:12 PM
  • 02 0277_02 0276_08092015_064332.mp4

Date
09/08/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02591
Time
6:12 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2738
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
22
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0277
Downstream MH
02 0276
Dir. of Survey
Downstream
Length Surveyed
388.8 ft.
Total Length
388.8 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 0277 to 02 0276
MH: 02 0277MH: 02 0276downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 02770 ft. MGO - General Observation - LATERAL AT MH 3 0CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area2.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start20.3 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES28.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start51.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"151 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"246.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"341.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"383.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish388.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish388.8 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK388.8 ft. AMH - Downstream Manhole, Survey Ends - 02 0276

Observations (15)

DistanceCodeObservation
0MWL
383.6CM
0AMH02 0277
0MGOLATERAL AT MH 3 0CLOCK
388.8DAGS
51.1TFC
388.8MGOLATERAL AT MH 9 OCLOCK
388.8AMH02 0276
20.3CM
0MWM
246.2TFC
151TFC
28.7CM
341.5TFC
2.7DAGS

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-09-08T06:12:49-07:00
documentation
PROPIPE
is_lateral_inspection
false