Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 23, 2015, 08:32 AM
  • 02 0194_02 0193_23092015_015308.mp4

Date
09/23/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02502
Time
1:32 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2750
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 0194
Downstream MH
02 0193
Dir. of Survey
Downstream
Length Surveyed
357.7 ft.
Total Length
357.7 ft.
Structural Index
2
Structural Quick
2111
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
3
Pipe schematic from manhole 02 0194 to 02 0193
MH: 02 0194MH: 02 0193downstream0 ft. MGO - General Observation - SERVICE LATERAL AT 3 O' CLOCK AT MH0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 019474.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"100.5 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES121.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"174.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"220.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"224 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"250.3 ft. CC - Crack Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES273.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"277 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"317.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"335.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"357.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0193

Observations (18)

DistanceCodeObservation
174.5TFC
121.9TFC
250.3CC
0MGOSERVICE LATERAL AT 3 O' CLOCK AT MH
0MWM
0MWL
224TFC
317.1TFC
0MWL
0MWM
74.8TFC
335.6TFC
277TFC
0AMH02 0194
220.7TF
100.5CL
357.7AMH02 0193
273.8TFC

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2015-09-23T01:32:53-07:00
documentation
PROPIPE
is_lateral_inspection
false