Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2015, 07:19 AM
  • 02 0202_02 0201_18092015_003636.mp4

Date
09/18/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02510
Time
12:19 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2748
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 0202
Downstream MH
02 0201
Dir. of Survey
Downstream
Length Surveyed
388 ft.
Total Length
388 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 0202 to 02 0201
MH: 02 0202MH: 02 0201downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 02020 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH24.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"27.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"79.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"82.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"122 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"124.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"146.8 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start173.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"176.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"216.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"219.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"268.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"271.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"320.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"323.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"330.7 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES333.5 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES369 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"372 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"388 ft. AMH - Downstream Manhole, Survey Ends - 02 0201388 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish

Observations (25)

DistanceCodeObservation
216.4TFC
0MWM
24.6TFC
369TF
146.8DSZ
27.4TF
176.6TFA
333.5CM
82.7TFC
173.7TFC
79.4TFC
388AMH02 0201
330.7CM
320.6TFC
219.4TF
122TFC
268.5TFC
0AMH02 0202
0MWL
323.4TFC
124.7TFA
0MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
271.5TFC
372TFC
388DSZ

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2015-09-18T00:19:50-07:00
documentation
PROPIPE
is_lateral_inspection
false