Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 24, 2015, 05:40 AM
  • 02 0188_02 0187_23092015_225516.mp4

Date
09/23/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02494
Time
10:40 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2751
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
32
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 0188
Downstream MH
02 0187
Dir. of Survey
Downstream
Length Surveyed
373.5 ft.
Total Length
373.5 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 02 0188 to 02 0187
MH: 02 0188MH: 02 0187downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CAPPED LATERAL AT 9 O' CLOCK AT0 ft. AMH - Upstream Manhole, Survey Begins - 02 01880 ft. MGO - General Observation - CAPPED LATERAL AT 3 O' CLOCK AT MH4 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES32.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"78.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"80 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES124.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"127.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"151.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"176.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"224.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"227.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"251.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"276.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"324.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"327.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"373.5 ft. AMH - Downstream Manhole, Survey Ends - 02 0187

Observations (20)

DistanceCodeObservation
227.7TFC
251.3TFA
151.8TF
224.8TFC
78.3TFC
0MWM
127.3TF
324.9TFA
0MWL
0MGOCAPPED LATERAL AT 9 O' CLOCK AT
373.5AMH02 0187
124.5TFC
32.4TFC
176.8TFC
327.6TFC
4CL
0AMH02 0188
0MGOCAPPED LATERAL AT 3 O' CLOCK AT MH
80CL
276.4TFC

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2015-09-23T22:40:34-07:00
documentation
PROPIPE
is_lateral_inspection
false