Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 24, 2015, 05:20 AM
  • 02 0190_02 0189_23092015_223309.mp4

Date
09/23/2015
W/O
521010
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00251
PipeID
P02497
Time
10:20 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2751
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
32
Purpose
Routine Assessment
Project
WO_521010_TV02055_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 0190
Downstream MH
02 0189
Dir. of Survey
Downstream
Length Surveyed
296.2 ft.
Total Length
296.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
0
Overall Quick
Overall Rating
0
Pipe schematic from manhole 02 0190 to 02 0189
MH: 02 0190MH: 02 0189downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 01900 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area16.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"19.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"80.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"126.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"129.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"187.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"190.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"224.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"227.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"267.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"271.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"296.2 ft. MGO - General Observation - SERVICE LATERAL AT 3 O' CLOCK AT MH296.2 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH296.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0189

Observations (18)

DistanceCodeObservation
129.2TF
296.2MGOSERVICE LATERAL AT 3 O' CLOCK AT MH
271.4TFC
126.3TF
19.2TFC
0AMH02 0190
77.3TF
16.3TF
0MWL
187.5TFC
190.3TFA
224.6TFC
296.2MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
227.6TFC
267.8TFC
80.7TFC
0MWM
296.2AMH02 0189

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2015-09-23T22:20:08-07:00
documentation
PROPIPE
is_lateral_inspection
false