Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 21, 2018, 07:56 AM
  • 32 0145A_32 0145 _21082018_010732.mp4

Date
08/21/2018
W/O
723911
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19894
Time
12:56 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6007
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
13
Purpose
Routine Assessment
Project
WO_723911_TV32048_SEP2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0145A
Downstream MH
32 0145
Dir. of Survey
Downstream
Length Surveyed
191.3 ft.
Total Length
191.3 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
114
O&M Index
2
O&M Quick
412G
O&M Rating
80
Overall Index
3
Overall Quick
Overall Rating
194
Pipe schematic from manhole 32 0145A to 32 0145
MH: 32 0145AMH: 32 0145downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 0145A0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start34.2 ft. MGO - General Observation - MAG COATING THROUGHOUT 60%191.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish191.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish191.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE191.3 ft. AMH - Downstream Manhole, Survey Ends - 32 0145

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    191.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
191.2SAP
2SAP
191.2DAGS
191.3MGOCOCKROACHES IN MANHOLE
0MWM
0MWL
2DAGS
191.3AMH32 0145
0AMH32 0145A
0MGOCOCKROACHES IN MANHOLE
34.2MGOMAG COATING THROUGHOUT 60%

Properties (6)

additional_info
SC364777
custom_field_two
2
customer
LACSD
datetime
2018-08-21T00:56:34-07:00
documentation
PRO PIPE
is_lateral_inspection
false