Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2018, 05:50 AM
  • 32 0137A_32 0137 _23082018_231420.mp4

Date
08/23/2018
W/O
723911
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19885
Time
10:50 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6016
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
WO_723911_TV32048_SEP2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 0137A
Downstream MH
32 0137
Dir. of Survey
Downstream
Length Surveyed
204.1 ft.
Total Length
204.1 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
120
O&M Index
2
O&M Quick
412G
O&M Rating
86
Overall Index
3
Overall Quick
Overall Rating
206
Pipe schematic from manhole 32 0137A to 32 0137
MH: 32 0137AMH: 32 0137downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 0137A0 ft. MWL - Water Level, 40 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start203.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish203.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish204.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE204.1 ft. AMH - Downstream Manhole, Survey Ends - 32 0137

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    204.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
2SAP
0MGOCOCKROACHES IN MANHOLE
0DAGS
0MWM
203.2DAGS
0AMH32 0137A
204.1MGOCOCKROACHES IN MANHOLE
0MWL
203.2SAP
204.1AMH32 0137

Properties (6)

additional_info
SC364780
custom_field_two
2
customer
LACSD
datetime
2018-08-23T22:50:31-07:00
documentation
PRO PIPE
is_lateral_inspection
false