Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 22, 2018, 06:18 AM
  • 32 0134_32 0133_21082018_233730.mp4

Date
08/21/2018
W/O
723911
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19882
Time
11:18 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6008
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
WO_723911_TV32048_SEP2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 0134
Downstream MH
32 0133
Dir. of Survey
Downstream
Length Surveyed
500 ft.
Total Length
500 ft.
Structural Index
3
Structural Quick
3S00
Structural Rating
297
O&M Index
2
O&M Quick
412S
O&M Rating
202
Overall Index
3
Overall Quick
Overall Rating
499
Pipe schematic from manhole 32 0134 to 32 0133
MH: 32 0134MH: 32 0133downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 01340 ft. MGO - General Observation - MAG COATING 50%0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start498.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish498.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish500 ft. AMH - Downstream Manhole, Survey Ends - 32 0133

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0AMH32 0134
2DAGS
498.6DAGS
500AMH32 0133
0MGOMAG COATING 50%
2SAP
498.6SAP
0MWM
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0MWL

Properties (6)

additional_info
SC364778
custom_field_two
2
customer
LACSD
datetime
2018-08-21T23:18:13-07:00
documentation
PRO PIPE
is_lateral_inspection
false