Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 22, 2018, 06:41 AM
  • 32 0133_32 0132A_21082018_235732.mp4

Date
08/21/2018
W/O
723911
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19881
Time
11:41 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6008
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
WO_723911_TV32048_SEP2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 0133
Downstream MH
32 0132A
Dir. of Survey
Downstream
Length Surveyed
73.5 ft.
Total Length
73.5 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
42
O&M Index
2
O&M Quick
412B
O&M Rating
32
Overall Index
3
Overall Quick
Overall Rating
74
Pipe schematic from manhole 32 0133 to 32 0132A
MH: 32 0133MH: 32 0132Adownstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 01330 ft. MWL - Water Level, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start71.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE71.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish71.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish73.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK73.5 ft. AMH - Downstream Manhole, Survey Ends - 32 0132A

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    71.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
0MWM
71.7MGOCOCKROACHES IN MANHOLE
0AMH32 0133
0MWL
71.7SAP
73.5MGOCONNECTION AT MH 9 O'CLOCK
2DAGS
2SAP
73.5AMH32 0132A
71.7DAGS

Properties (6)

additional_info
SC364778
custom_field_two
2
customer
LACSD
datetime
2018-08-21T23:41:46-07:00
documentation
PRO PIPE
is_lateral_inspection
false