Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 2, 2019, 08:01 AM
  • B 0658_B 0657A _02042019_010202.mp4

Date
04/02/2019
W/O
756630
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00109
PipeID
P09327
Time
1:01 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5842
Sewer Name
B JOINT OUTFALL B - UNIT 8F
City
ARCADIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
12
Purpose
Routine Assessment
Project
WO_756630_TV15056_MAR2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
B 0658
Downstream MH
B 0657A
Dir. of Survey
Downstream
Length Surveyed
333.5 ft.
Total Length
333.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole B 0658 to B 0657A
MH: B 0658MH: B 0657Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - B 06580 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.5 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start - MAG COATNG95.6 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start148.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"331.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish331.8 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish331.8 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish333.5 ft. AMH - Downstream Manhole, Survey Ends - B 0657A333.5 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start - MAG COATNG

    2.5 ft. - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start - MAG COATNG

Observations (13)

DistanceCodeObservation
95.6DSC
0AMHB 0658
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
331.8DAGS
0MWL
0MWM
331.8DSC
331.8DAZ
148.9TB
2.4DAGS
2.5DAZMAG COATNG
333.5AMHB 0657A
333.5MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH

Properties (6)

additional_info
SC366079
custom_field_two
5
customer
LACSD
datetime
2019-04-02T01:01:45-07:00
documentation
PROPIPE
is_lateral_inspection
false