Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 2, 2019, 09:14 AM
  • B 0655_B 0654 _02042019_021542.mp4

Date
04/02/2019
W/O
756630
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00109
PipeID
P09323
Time
2:14 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5842
Sewer Name
B JOINT OUTFALL B - UNIT 8F
City
ARCADIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
12
Purpose
Routine Assessment
Project
WO_756630_TV15056_MAR2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
B 0654
Downstream MH
B 0655
Dir. of Survey
Upstream
Length Surveyed
330.9 ft.
Total Length
330.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole B 0654 to B 0655
MH: B 0654MH: B 0655upstream0 ft. AMH - Upstream Manhole, Survey Ends - B 06552.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.3 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish54.6 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"164.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"327.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start327.4 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start - MAG COATING330.9 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH330.9 ft. AMH - Downstream Manhole, Survey Begins - B 0654330.9 ft. MWL - Water Level, 20 %of cross sectional area330.9 ft. MWM - Water Mark, 35 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start - MAG COATING

    3.5 ft. - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start - MAG COATING

Observations (11)

DistanceCodeObservation
276.3TFA
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
166.2TB
3.5DAGS
0AMHB 0654
0MWL
330.9AMHB 0655
328.6DAGS
328.6DAZ
3.5DAZMAG COATING
0MWM

Properties (6)

additional_info
SC366079
custom_field_two
5
customer
LACSD
datetime
2019-04-02T02:14:54-07:00
documentation
PROPIPE
is_lateral_inspection
false