Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 10, 2018, 06:05 AM
  • 05 1045_05 0115 _09102018_233506.mpg

Date
10/09/2018
W/O
729726
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00441
PipeID
P06280
Time
11:05 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6139
Sewer Name
05 FLOWER STREET TRUNK
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_729726_TV05195_OCT2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 1045
Downstream MH
05 0115
Dir. of Survey
Downstream
Length Surveyed
335.5 ft.
Total Length
335.5 ft.
Structural Index
4
Structural Quick
5141
Structural Rating
12
O&M Index
2
O&M Quick
4113
O&M Rating
7
Overall Index
3
Overall Quick
Overall Rating
19
Pipe schematic from manhole 05 1045 to 05 0115
MH: 05 1045MH: 05 0115downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 10450 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2.7 ft. RFJ - Roots Fine Joint, from 08 to 01 o'clock, within 8 inches of joint: YES2.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"12.2 ft. B - Broken, from 07 to 10 o'clock, within 8 inches of joint: NO13.6 ft. RBL - Roots Ball Lateral, at 10 o'clock, 80 %13.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"14.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start54.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"83.5 ft. FM - Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES84.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"140 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"142.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"187.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"192.7 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish209.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"211.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"257.7 ft. RFL - Roots Fine Lateral, at 10 o'clock257.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"260.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"296.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"299.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"335.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish335.5 ft. AMH - Downstream Manhole, Survey Ends - 05 0115

Observation photos (5)

  • Roots Fine Joint, from 08 to 01 o'clock, within 8 inches of joint: YES

    2.7 ft. - Roots Fine Joint, from 08 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 07 to 10 o'clock, within 8 inches of joint: NO

    12.2 ft. - Broken, from 07 to 10 o'clock, within 8 inches of joint: NO

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    14.6 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

    83.5 ft. - Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

Observations (29)

DistanceCodeObservation
0MWM
142.1TF
2.7RFJ
13.6RBL
0MWL
84.6TF
0MGOCONNECTION AT MH 3 O'CLOCK
13.6TF
140TFC
192.7RFJ
260.3TF
2.7CM
54.7TF
12.2B
14.6RFJ
0AMH05 1045
296.8TF
257.7RFL
10.3TF
0MGOCONNECTION AT MH 9 O'CLOCK
335.5CM
211.8TF
187.7TF
335.5AMH05 0115
257.7TF
299.5TFC
83.5FM
209.4TFC
128.3TFC

Properties (6)

additional_info
SC365206
custom_field_two
2
customer
LACSD
datetime
2018-10-09T23:05:44-07:00
documentation
PROPIPE
is_lateral_inspection
false