Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 11, 2018, 10:09 AM
  • 21 0259_21 0258A _11092018_032045.mp4

Date
09/11/2018
W/O
724275
Weather
Dry
Operator/Surveyor
B. FUGATE
Sewer ID
Z00763
PipeID
P23062
Time
3:09 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6000
Sewer Name
21 DISTRICT #21 OUTFALL TRUNK
City
CITY OF INDUSTRY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
36
Purpose
Routine Assessment
Project
WO_724275_TV21103_SEP2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
21 0259
Downstream MH
21 0258A
Dir. of Survey
Downstream
Length Surveyed
293.8 ft.
Total Length
293.8 ft.
Structural Index
4
Structural Quick
5I3K
Structural Rating
419
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
419
Pipe schematic from manhole 21 0259 to 21 0258A
MH: 21 0259MH: 21 0258Adownstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 21 02593.7 ft. MGO - General Observation - MAG COAT - 30%3.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start29.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"38.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"48 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start86 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"93.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"134.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"142.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"190.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"198.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"246.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"254.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"293.8 ft. MGO - General Observation - UNKNOWN CONNECTION AT MH 9 O'CLOCK293.8 ft. AMH - Downstream Manhole, Survey Ends - 21 0258A293.8 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK293.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish293.8 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    48 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
190.4TFC
93.5TFC
293.8MGOUNKNOWN CONNECTION AT MH 9 O'CLOCK
293.8AMH21 0258A
0MWM
293.8MGOACTIVE CONNECTION AT MH 3 O'CLOCK
198.6TFC
29.9TFC
48SRV
0MWL
38.6TFC
86TFC
3.7MGOMAG COAT - 30%
293.8SAP
142.3TFC
293.8SRV
0AMH21 0259
134.4TFC
254.6TFC
246.4TFC
3.7SAP

Properties (6)

additional_info
SC364815
custom_field_two
2
customer
LACSD
datetime
2018-09-11T03:09:00-07:00
documentation
PROPIPE
is_lateral_inspection
false