Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 22, 2019, 09:42 AM
  • 02 1844_02 1843_01222019_020051.mp4

Date
01/22/2019
W/O
745535
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00283
PipeID
P04189
Time
1:42 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5342
Sewer Name
02 MONTEBELLO INTERCEPTOR TRUNK, SECTS 1&2
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_745535_TV02214_JAN2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
02 1844
Downstream MH
02 1843
Dir. of Survey
Downstream
Length Surveyed
92 ft.
Total Length
92 ft.
Structural Index
5
Structural Quick
5B00
Structural Rating
80
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
84
Pipe schematic from manhole 02 1844 to 02 1843
MH: 02 1844MH: 02 1843downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 18440 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area8 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start88.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish92 ft. AMH - Downstream Manhole, Survey Ends - 01 1843

Observation photos (1)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    8 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
8SRV
0AMH02 1844
88.1SRV
0MWM
0MWL
92AMH01 1843

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-01-22T01:42:13-08:00
documentation
PROPIPE
is_lateral_inspection