Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2019, 04:18 PM
  • 05 0472_05 0471_8132019_092200.mp4

Date
08/13/2019
W/O
0786503
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00526
PipeID
P05687
Time
9:18 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8053
Sewer Name
05 STRAWBERRY AVENUE TRUNK
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
20190812DF_STRAWBERRY_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
05 0471
Downstream MH
05 0472
Dir. of Survey
Upstream
Length Surveyed
299.6 ft.
Total Length
299.6 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 05 0471 to 05 0472
MH: 05 0471MH: 05 0472upstream0 ft. MGO - General Observation - Grease Throughout The Reach (5%)0 ft. AMH - Upstream Manhole, Survey Ends - 9:50 AM1.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish11.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open13.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"52.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"65.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open82.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open103.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open134 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open165 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"177.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open187.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"190.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open206.3 ft. MGP - General Photograph235.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"254.6 ft. MGP - General Photograph263.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"297.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start297.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start299.6 ft. MWM - Water Mark, 15 %of cross sectional area299.6 ft. MWL - Water Level, 10 %of cross sectional area299.6 ft. MGO - General Observation - ROACHES @ MH299.6 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active299.6 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active299.6 ft. AMH - Downstream Manhole, Survey Begins - 9:19 AM

Observation photos (6)

  • Downstream Manhole, Survey Begins - 9:19 AM

    0 ft. - Downstream Manhole, Survey Begins - 9:19 AM

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    45 ft. - General Photograph

  • General Photograph

    93.3 ft. - General Photograph

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open

    109.5 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open

Observations (27)

DistanceCodeObservation
288.4TFOpen
45MGP
109.5TBOpen
0MWM
0MWL
0MGOROACHES @ MH
216.8TFOpen
299.6MGOGrease Throughout The Reach (5%)
134.6TFA
93.3MGP
0MGOConn. @ Mh, 3 O' Clock. Active
63.7TFC
2SSS
196.2TFOpen
0MGOConn. @ Mh, 9 O' Clock. Active
299.6AMH9:50 AM
0AMH9:19 AM
112.4TFC
2CM
297.8SSS
35.7TFC
247.1TFA
285.7TFA
122.2TFOpen
234.3TFOpen
297.8CM
165.6TFOpen

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-08-13T09:18:29-07:00
documentation
FRANKLIN, CASTILLO, RUVALCABA
is_lateral_inspection