Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2019, 05:32 PM
  • 05 0467_05 0466_8122019_103629.mp4

Date
08/12/2019
W/O
0786503
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00526
PipeID
P05682
Time
10:32 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8052
Sewer Name
05 STRAWBERRY AVENUE TRUNK
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
20190812DF_STRAWBERRY_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
05 0467
Downstream MH
05 0466
Dir. of Survey
Downstream
Length Surveyed
291.6 ft.
Total Length
291.6 ft.
Structural Index
3
Structural Quick
3421
Structural Rating
14
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
18
Pipe schematic from manhole 05 0467 to 05 0466
MH: 05 0467MH: 05 0466downstream0 ft. AMH - Upstream Manhole, Survey Begins - 10:34 AM0.1 ft. MWM - Water Mark, 15 %of cross sectional area0.1 ft. MWL - Water Level, 10 %of cross sectional area0.1 ft. MGO - General Observation - ROACHES @ MH2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start15.8 ft. TFD - Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Active19.8 ft. MGP - General Photograph21.6 ft. TFD - Tap Factory Made Defective, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open72.9 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 4"89.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES106.3 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 4"135.6 ft. MGP - General Photograph151.1 ft. FS - Fracture Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES152.4 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Open157.4 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open175.4 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 4"205.1 ft. FS - Fracture Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES206.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Open254.6 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 4"257.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"287.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish287.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish291.6 ft. MGO - General Observation - ROACHES @ MH291.6 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN291.6 ft. MGO - General Observation - Grease Throughout The Reach (5%)291.6 ft. AMH - Downstream Manhole, Survey Ends - 11:03 AM291.6 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active

Observation photos (10)

  • Upstream Manhole, Survey Begins - 10:34 AM

    0 ft. - Upstream Manhole, Survey Begins - 10:34 AM

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Active

    15.8 ft. - Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Active

  • General Photograph

    19.8 ft. - General Photograph

  • Tap Factory Made Defective, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open

    21.6 ft. - Tap Factory Made Defective, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    89.6 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • General Photograph

    135.6 ft. - General Photograph

  • Fracture Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

    151.1 ft. - Fracture Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

    205.1 ft. - Fracture Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

Observations (28)

DistanceCodeObservation
257.2TFC
175.4TFA
89.6FL
135.6MGP
287.7CM
254.6TFC
291.6MGOROACHES @ MH
0.1MWM
157.4TFOpen
0.1MWL
291.6MGOConn. @ Mh, 3 O' Clock. OPEN
0.1MGOROACHES @ MH
72.9TFA
2CM
291.6MGOGrease Throughout The Reach (5%)
206.1TFOpen
152.4TFOpen
291.6AMH11:03 AM
106.3TFA
15.8TFDActive
205.1FS
19.8MGP
287.7SSS
151.1FS
0AMH10:34 AM
291.6MGOConn. @ Mh, 9 O' Clock. Active
2SSS
21.6TFDOpen

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-08-12T10:32:28-07:00
documentation
FRANKLIN, CASTILLO, RUVALCABA
is_lateral_inspection
false