Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 15, 2019, 10:07 AM
  • Section#10_E 0113_E 0112__8152019__I0217.mp4

Date
08/15/2019
W/O
0784628
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00032
PipeID
P11339
Time
3:07 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0217
Sewer Name
E JOINT OUTFALL E - UNIT 5
City
WILLOWBROOK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
20190813MDM_JOINT_OUTFALL_E_UNIT_5
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
E 0113
Downstream MH
E 0112
Dir. of Survey
Downstream
Length Surveyed
570.8 ft.
Total Length
570.8 ft.
Structural Index
2
Structural Quick
522V
Structural Rating
242
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
242
Pipe schematic from manhole E 0113 to E 0112
MH: E 0113MH: E 0112downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:40AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT2 ft. MGO - General Observation - 99% MAG COAT START35.7 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE UNDER MAG COAT76.2 ft. SSS - Surface Spalling, from 02 to 04 o'clock, within 8 inches of joint: YES - BLISTERING CONCRETE158.7 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - POSSIBLE CIRCUM REBAR UNDER MAG COAT375 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN422.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN448.2 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - POSSIBLE CIRCUM REBAR UNDER MAG COAT466.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE518.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE570.2 ft. MGO - General Observation - MH CONN 3:00 ACTIVE570.2 ft. MGO - General Observation - 99% MAG COAT FINISH570.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE UNDER NAG COAT570.8 ft. AMH - Downstream Manhole, Survey Ends - 5:20AM

Observation photos (6)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • General Observation - 99% MAG COAT START

    2 ft. - General Observation - 99% MAG COAT START

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE UNDER MAG COAT

    35.7 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE UNDER MAG COAT

  • Surface Spalling, from 02 to 04 o'clock, within 8 inches of joint: YES - BLISTERING CONCRETE

    76.2 ft. - Surface Spalling, from 02 to 04 o'clock, within 8 inches of joint: YES - BLISTERING CONCRETE

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - POSSIBLE CIRCUM REBAR UNDER MAG COAT

    158.7 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - POSSIBLE CIRCUM REBAR UNDER MAG COAT

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - POSSIBLE CIRCUM REBAR UNDER MAG COAT

    448.2 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: YES - POSSIBLE CIRCUM REBAR UNDER MAG COAT

Observations (17)

DistanceCodeObservation
570.2MGOMH CONN 3:00 ACTIVE
466.4TFACTIVE
158.7SRVPOSSIBLE CIRCUM REBAR UNDER MAG COAT
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
448.2SRVPOSSIBLE CIRCUM REBAR UNDER MAG COAT
570.2MGO99% MAG COAT FINISH
570.2SSSBLISTERING PEELING CONCRETE UNDER NAG COAT
0AMH4:40AM
76.2SSSBLISTERING CONCRETE
35.7SSSBLISTERING CONCRETE UNDER MAG COAT
375TFOPEN
0MWM
570.8AMH5:20AM
2MGO99% MAG COAT START
0MWL
518.6TFACTIVE
422.6TFOPEN

Properties (6)

custom_field_three
SPALLING-POSSIBLE SURFACE CIRCUM REBAR-99% MAG COA
custom_field_two
3
customer
LACSD
datetime
2019-08-15T03:07:15-07:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection
false