Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 10, 2018, 07:31 AM
  • 04 0084_04 0083A _10102018_003215.mp4

Date
10/10/2018
W/O
729263
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00415
PipeID
P11823
Time
12:31 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6161
Sewer Name
04 SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_729263_TV04021_OCT2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
04 0083A
Downstream MH
04 0084
Dir. of Survey
Upstream
Length Surveyed
130.9 ft.
Total Length
130.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2D00
O&M Rating
50
Overall Index
2
Overall Quick
Overall Rating
50
Pipe schematic from manhole 04 0083A to 04 0084
MH: 04 0083AMH: 04 0084upstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Ends - 04 00840 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK2.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish64 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"105.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"107.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start130.9 ft. MGO - General Observation - UNKNOWN DROP CONNECTION INSIDE THE MANHOLE AT 02 O'CLOCK130.9 ft. AMH - Downstream Manhole, Survey Begins - 04 0083A130.9 ft. MWL - Water Level, 20 %of cross sectional area130.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE130.9 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    130.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (13)

DistanceCodeObservation
128DAGS
2DAGS
0MGOUNKNOWN DROP CONNECTION INSIDE THE MANHOLE AT 02 O'CLOCK
0AMH04 0083A
130.9MGOCOCKROACHES IN MANHOLE
25.8TFC
130.9AMH04 0084
0MWL
0MGOCOCKROACHES IN MANHOLE
23TFC
130.9MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWM
66.9TFC

Properties (6)

additional_info
SC365129
custom_field_two
3
customer
LACSD
datetime
2018-10-10T00:31:52-07:00
documentation
PRO PIPE
is_lateral_inspection
false