Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 10, 2018, 08:10 AM
  • 04 0081_04 0080 _10102018_011302.mp4

Date
10/10/2018
W/O
729263
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00415
PipeID
P11819
Time
1:10 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6161
Sewer Name
04 SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_729263_TV04021_OCT2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
04 0081
Downstream MH
04 0080
Dir. of Survey
Downstream
Length Surveyed
352.5 ft.
Total Length
352.5 ft.
Structural Index
3
Structural Quick
523J
Structural Rating
175
O&M Index
2
O&M Quick
4131
O&M Rating
234
Overall Index
2
Overall Quick
Overall Rating
409
Pipe schematic from manhole 04 0081 to 04 0080
MH: 04 0081MH: 04 0080downstream0 ft. AMH - Upstream Manhole, Survey Begins - 04 00810 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.2 ft. RBJ - Roots Ball Joint, from 09 to 03 o'clock, 55 %, within 8 inches of joint: YESR9.8 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR20.2 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES20.2 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start21.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"32 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"64.1 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES68.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"73.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"82.3 ft. CS - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES90.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES92.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start114.1 ft. RFL - Roots Fine Lateral, from 01 to 04 o'clock114.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"116.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"119.1 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"160 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6" - ACTIVE WITH FRACTURE INSIDE THE TAP162.4 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"168.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"203.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"206.3 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"249.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"252.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"253.8 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish273.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start277.8 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"295.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"297.8 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 12 o'clock, , within 8 inches of joint: NO - BLOCKING 40% OF TAP297.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"304.4 ft. H - Hole, from 01 to 04 o'clock, within 8 inches of joint: YES327 ft. H - Hole, from 01 to 04 o'clock, within 8 inches of joint: YES - FILLED IN WITH POSSIBLE ENCRUSTATION341.4 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS341.4 ft. RML - Roots Medium Lateral, from 07 to 11 o'clock, 10 %, within 8 inches of joint: NO346.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"351.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish351.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish351.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish352.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE352.5 ft. AMH - Downstream Manhole, Survey Ends - 04 0080

Observation photos (16)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Roots Ball Joint, from 09 to 03 o'clock, 55 %, within 8 inches of joint: YESR

    4.2 ft. - Roots Ball Joint, from 09 to 03 o'clock, 55 %, within 8 inches of joint: YESR

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR

    9.8 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    20.2 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    20.2 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    64.1 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    82.3 ft. - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    90.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    92.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Lateral, from 01 to 04 o'clock

    114.1 ft. - Roots Fine Lateral, from 01 to 04 o'clock

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    273.5 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 12 o'clock,  , within 8 inches of joint: NO - BLOCKING 40% OF TAP

    297.8 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 12 o'clock, , within 8 inches of joint: NO - BLOCKING 40% OF TAP

  • Hole, from 01 to 04 o'clock, within 8 inches of joint: YES

    304.4 ft. - Hole, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Roots Medium Lateral, from 07 to 11 o'clock, 10 %, within 8 inches of joint: NO

    341.4 ft. - Roots Medium Lateral, from 07 to 11 o'clock, 10 %, within 8 inches of joint: NO

  • General Observation - COCKROACHES IN MANHOLE

    352.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (45)

DistanceCodeObservation
20.2CL
352.5MGOCOCKROACHES IN MANHOLE
114.1RFL
0AMH04 0081
2DAGS
90.1CM
253.8RFJ
32TBA
168.5TBA
68.1TFA
20.2RFJ
0MGOCOCKROACHES IN MANHOLE
304.4H
119.1TBA
203.9TFC
249.3TFA
295.3TFC
206.3TFA
4.2RBJ
327HFILLED IN WITH POSSIBLE ENCRUSTATION
0MGOCONNECTION AT MH 9 O'CLOCK
160TFDACTIVE WITH FRACTURE INSIDE THE TAP
346.8TFA
9.8RFJ
297.8DAEBLOCKING 40% OF TAP
297.8TF
273.5DAE
341.4TFDROOTS
82.3CS
21.4TFC
341.4RML
352.5AMH04 0080
252.1TFA
64.1CL
162.4TFA
0MWM
277.8TBA
351.7DAGS
73.2TFA
351.7DAE
351.7CM
92.4CM
114.1TFA
0MWL
116.8TF

Properties (6)

additional_info
SC365129
custom_field_two
1
customer
LACSD
datetime
2018-10-10T01:10:37-07:00
documentation
PRO PIPE
is_lateral_inspection
false