Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 8, 2018, 08:48 AM
  • 04 0077_04 0076 _08102018_014940.mp4

Date
10/08/2018
W/O
729263
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00415
PipeID
P11814
Time
1:48 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6136
Sewer Name
04 SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_729263_TV04021_OCT2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
04 0077
Downstream MH
04 0076
Dir. of Survey
Downstream
Length Surveyed
241 ft.
Total Length
241 ft.
Structural Index
4
Structural Quick
4H00
Structural Rating
188
O&M Index
2
O&M Quick
322I
O&M Rating
108
Overall Index
3
Overall Quick
Overall Rating
296
Pipe schematic from manhole 04 0077 to 04 0076
MH: 04 0077MH: 04 0076downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 04 00770 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start65.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"100.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"128.5 ft. RML - Roots Medium Lateral, from 09 to 12 o'clock, 20 %, within 8 inches of joint: YES128.5 ft. TBD - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: NO, 6"128.7 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR138.5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"146 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"148.8 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6", 6" - OFFSET IN THE TAP202.2 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6", 6" - OFFSET WITH POSSIBLE SOIL VISIBLE204.8 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"206.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"206.7 ft. RFL - Roots Fine Lateral, from 07 to 11 o'clock206.7 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 6"235.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"239.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish239.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish239.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE241 ft. AMH - Downstream Manhole, Survey Ends - 04 0076

Observation photos (8)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Lateral, from 09 to 12 o'clock, 20 %, within 8 inches of joint: YES

    128.5 ft. - Roots Medium Lateral, from 09 to 12 o'clock, 20 %, within 8 inches of joint: YES

  • Tap Break-In Defective, at 10 o'clock, -,  , within 8 inches of joint: NO, 6"

    128.5 ft. - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: NO, 6"

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR

    128.7 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR

  • Roots Fine Lateral, from 07 to 11 o'clock

    206.7 ft. - Roots Fine Lateral, from 07 to 11 o'clock

  • General Observation - COCKROACHES IN MANHOLE

    239.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (25)

DistanceCodeObservation
202.2TFDOFFSET WITH POSSIBLE SOIL VISIBLE
3.4FM
128.7RFJ
128.5RML
239.1DAGS
148.8TFDOFFSET IN THE TAP
146TFC
2DAGS
0MWM
206.7TBA
239.1FM
204.8TBA
239.1MGOCOCKROACHES IN MANHOLE
65.4TFC
206.7RFL
241AMH04 0076
235.3TFC
0MGOCOCKROACHES IN MANHOLE
100.6TFC
0MGOACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK
206.7TFD
128.5TBD
0AMH04 0077
0MWL
138.5TBA

Properties (6)

additional_info
SC365122
custom_field_two
3
customer
LACSD
datetime
2018-10-08T01:48:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false